Reference · Fire safety

Fire-hose coupling standards, sizes and pressure ratings

A quick reference for the coupling types found aboard ship. Always confirm a coupling from its stamped markings and the ship's approved equipment list before relying on any figure here. For inspection and removal criteria, read the fire-hose couplings lesson.

At a glance

TypeStandardPressure rating
Claw / Storz-type (symmetrical)DIN 14301, 14302, 14303 (Germany); EN 14420-8Set by the manufacturer and marked or certified for each product.
Instantaneous (push-in)BS 336 (UK)Set by the manufacturer and marked or certified for each product.
Threaded (NH / NST)NFPA 1963 (USA)Set by the manufacturer and marked or certified for each product.
International shore connectionSOLAS II-2/10; FSS Code, chapter 2Design pressure 1.0 N/mm² (about 10 bar).

Claw / Storz-type (symmetrical)

DIN 14301, 14302, 14303 (Germany); EN 14420-8

Identical halves, quarter turn to lock. Mating is set by claw spacing.

SizeHose boreClaw spacing
D25 mm31 mm
C 4242 mm66 mm
C 5252 mm66 mm
B75 mm89 mm
A110 mm133 mm

C 42 and C 52 share the 66 mm claw spacing and connect to each other. Different letters never mate without an approved adapter.

Pressure: Set by the manufacturer and marked or certified for each product.

Instantaneous (push-in)

BS 336 (UK)

Male and female halves push together and latch; release by lever or ring.

Nominal sizeApprox. boreTypical use
1¾ in45 mmAccommodation and light hoses
2½ in64–65 mmMost common shipboard fire hose

Does not mate with Storz-type or threaded couplings.

Pressure: Set by the manufacturer and marked or certified for each product.

Threaded (NH / NST)

NFPA 1963 (USA)

Male and female threads screwed together by hand or spanner.

Hose sizeThread diameterThreads per inch
1½ in1.990 in11.5
2½ in3.0686 in7.5

Look-alike threads of other standards cross-thread or leak.

Pressure: Set by the manufacturer and marked or certified for each product.

International shore connection

SOLAS II-2/10; FSS Code, chapter 2

Standard flange on the shore side; ship side fits the ship's own hydrants or hoses.

FeatureRequirement
Flange outside diameter178 mm
Flange inside diameter64 mm
Bolt circle diameter132 mm
Slots4 holes, 19 mm, equally spaced, slotted to the flange edge
Flange thicknessat least 14.5 mm
Bolts and nuts4 sets, 16 mm diameter, 50 mm long, plus 8 washers

The only coupling with internationally fixed dimensions, so any port can supply the fire main.

Pressure: Design pressure 1.0 N/mm² (about 10 bar).

How pressure ratings work

  • The coupling standards set dimensions, not one pressure for every product.
  • Working and test pressures come from the manufacturer's marking, data sheet or type-approval certificate.
  • Hoses and couplings must be rated for at least the fire main's maximum pressure.
  • Test pressures and intervals follow the planned maintenance system and flag-State requirements.

Sources: SOLAS Chapter II-2, FSS Code chapter 2, DIN 14301–14303, EN 14420-8, BS 336, NFPA 1963. Check figures against your own copies of these standards.