Reference · Fire safety
Fire-hose coupling standards, sizes and pressure ratings
A quick reference for the coupling types found aboard ship. Always confirm a coupling from its stamped markings and the ship's approved equipment list before relying on any figure here. For inspection and removal criteria, read the fire-hose couplings lesson.
At a glance
| Type | Standard | Pressure rating |
|---|---|---|
| Claw / Storz-type (symmetrical) | DIN 14301, 14302, 14303 (Germany); EN 14420-8 | Set by the manufacturer and marked or certified for each product. |
| Instantaneous (push-in) | BS 336 (UK) | Set by the manufacturer and marked or certified for each product. |
| Threaded (NH / NST) | NFPA 1963 (USA) | Set by the manufacturer and marked or certified for each product. |
| International shore connection | SOLAS II-2/10; FSS Code, chapter 2 | Design pressure 1.0 N/mm² (about 10 bar). |
Claw / Storz-type (symmetrical)
DIN 14301, 14302, 14303 (Germany); EN 14420-8
Identical halves, quarter turn to lock. Mating is set by claw spacing.
| Size | Hose bore | Claw spacing |
|---|---|---|
| D | 25 mm | 31 mm |
| C 42 | 42 mm | 66 mm |
| C 52 | 52 mm | 66 mm |
| B | 75 mm | 89 mm |
| A | 110 mm | 133 mm |
C 42 and C 52 share the 66 mm claw spacing and connect to each other. Different letters never mate without an approved adapter.
Pressure: Set by the manufacturer and marked or certified for each product.
Instantaneous (push-in)
BS 336 (UK)
Male and female halves push together and latch; release by lever or ring.
| Nominal size | Approx. bore | Typical use |
|---|---|---|
| 1¾ in | 45 mm | Accommodation and light hoses |
| 2½ in | 64–65 mm | Most common shipboard fire hose |
Does not mate with Storz-type or threaded couplings.
Pressure: Set by the manufacturer and marked or certified for each product.
Threaded (NH / NST)
NFPA 1963 (USA)
Male and female threads screwed together by hand or spanner.
| Hose size | Thread diameter | Threads per inch |
|---|---|---|
| 1½ in | 1.990 in | 11.5 |
| 2½ in | 3.0686 in | 7.5 |
Look-alike threads of other standards cross-thread or leak.
Pressure: Set by the manufacturer and marked or certified for each product.
International shore connection
SOLAS II-2/10; FSS Code, chapter 2
Standard flange on the shore side; ship side fits the ship's own hydrants or hoses.
| Feature | Requirement |
|---|---|
| Flange outside diameter | 178 mm |
| Flange inside diameter | 64 mm |
| Bolt circle diameter | 132 mm |
| Slots | 4 holes, 19 mm, equally spaced, slotted to the flange edge |
| Flange thickness | at least 14.5 mm |
| Bolts and nuts | 4 sets, 16 mm diameter, 50 mm long, plus 8 washers |
The only coupling with internationally fixed dimensions, so any port can supply the fire main.
Pressure: Design pressure 1.0 N/mm² (about 10 bar).
How pressure ratings work
- The coupling standards set dimensions, not one pressure for every product.
- Working and test pressures come from the manufacturer's marking, data sheet or type-approval certificate.
- Hoses and couplings must be rated for at least the fire main's maximum pressure.
- Test pressures and intervals follow the planned maintenance system and flag-State requirements.
Sources: SOLAS Chapter II-2, FSS Code chapter 2, DIN 14301–14303, EN 14420-8, BS 336, NFPA 1963. Check figures against your own copies of these standards.